A user facility biomedical technician (biomed) reported that a 2008t hemodialysis machine had a melted ultrafiltration (uf) check valve.
The biomed stated water was leaking from the back of the machine during heat disinfect.
There was no patient involvement associated with the event.
The biomed traced the leak to the ultrafiltration (uf) check valve.
The biomed stated the check valve had come apart and was melted.
The biomed stated the damage must have occurred from repeated heat disinfect cycles.
No damage was identified on any other components.
The biomed confirmed there was no burning smell or burn damage found.
Additionally, there were no signs of any smoke, sparks, or flames.
The biomed fixed the machine by replacing the check valve.
The machine was plugged into a hospital grade ground-fault circuit interrupter (gfci) outlet and had no previous history of failing the electrical leakage test.
The biomed stated the machine has approximately 22,000 to 24,000 hours on it.
It was confirmed the machine was returned to service.
Photographs of the damaged check valve were not available.
The biomed stated the part would be returned for evaluation via returned goods authorization (rga).
|