Analysis of a generator explanted for end of service was completed on (b)(4) 2014.The supply current tests did not meet functional specifications.These measurements demonstrate an increased current consumption for the device, potentially contributing to a premature end of life condition.The increased current consumption was isolated to a leaky capacitor (c4).A battery life estimation resulted in 0.48 years remaining before the eri flag would be set.However, an incomplete programming history indicates the estimation does not use all the data required to make an accurate estimation.With the capacitor substitution for c4, the pulse generator module performed according to functional specifications.The most probable root cause for the premature end of life condition was identified to be a leaky capacitor, c4.The cause for the c4 capacitors increase in leakage could not be determined.
|