It was reported that the biomed received an arctic sun device with a note on it stating that the device would not heat the water.
The reservoir level was showing five bars, and there were multiple alert 113s (reduced water temperature control) in the event log.
Per troubleshooting with ms&s, the biomed was walked through draining and refilling the device with the same water.
The device was over filled by 500ml.
Manual control was enabled with the water temperature set to 40c for 30 minutes.
T1 and t2 were 19.
1c but quickly rose to 37c.
T4 was 5.
8c.
With only the fluid delivery line attached, the flow rate was 1.
6l/min, the inlet pressure was -7psi, and the circulation pump command was 54%.
The pump hours were noted at 4676 and system hours noted at 4869.
Manual control was disabled.
|