The table subject of the reported event was removed from service.The user facility was concerned of burning because the pump motor was still running and a smell from the table was beginning to occur.Facility personnel were advised by the steris surgical service representative to press the cb2 breaker and stop battery power to the pump.The warning label on the table's column shroud states, "unanticipated table movement hazard- to remove all power from pump motor, disconnect power cord and interrupt circuit breaker (cb-2)." a steris surgical service representative inspected the table and found the override control switches to be corroded.The corrosion to the override control switches is indicative of fluid intrusion.In addition to the damaged override switches, the steris surgical service representative stated that the shrouds had evidence of impact damage from possible storage on the base.Due to the damage to the shroud, user facility personnel serviced the table by using silicon to seal the gaps between the shroud and bellows.The table was not properly sealed subsequently allowing entry points for fluid.The service representative repaired the table, tested it and returned it to service.No additional issues have been reported.While onsite the user facility was made aware of the importance of properly using rtv.The table is not under steris service contract and is serviced and maintained by the user facility.
|