The secondary motor cam follower, by default, is set to the bottom dead center (bdc) position during the manufacturing process.However, upon inspection at syncardia, the secondary motor was found to be moved out of the bdc position.The physical damage found on the unit and the position of the secondary motor indicated that the likely root cause of the customer-reported fault alarm was an impact shock to the driver.Despite the damage observed on the driver, the driver passed all performance testing requirements with no anomalies or alarms.In addition, the secondary motor was tested to confirm proper operation of all electronics, and the driver met all pressure test acceptance criteria at normotensive and hypertensive settings.The driver performed as intended and there was no evidence of a device malfunction.Review of the eeprom data and failure investigation testing indicated that there was likely an impact shock to the driver, causing the secondary cam follower to move out of bdc position during operation.The driver switched from the primary motor to the secondary motor, resulting in the 'secondary motor voltage too high' alarm.The motor/gearbox assemblies and print circuit assembly (pca) were replaced as a precautionary measure and the driver passed all final performance testing.Despite the customer-reported fault alarm, risk to the patient was low because the driver continued to perform its life-sustaining functions.This issue will be monitored and trended as part of the customer experience process.Syncardia has completed its evaluation of this complaint and is closing this file.
|