No injury or procedural delays or cancellations was reported.A steris service technician arrived at the facility, inspected the washer and found two washer fuses had tripped rendering the recirculation pump within the washer inoperable.The user facility stated a generator test was conducted prior to the reported event which caused a sudden power interruption.The steris technician was unable to confirm the cause of the tripped fuses, however stated the sudden power interruption may be related to the reported event.The technician replaced the two fuses, tested the washer and confirmed the unit was operating according to specification.The facility confirmed the cycle subject of the event was the only cycle impacted by the tripped fuses.The issue was identified during the inspection of instruments after the washing cycle was completed as described in section 4.8 of the reliance synergy operator manual.The reliance synergy operator manual section 4.8 states "visual inspection: important: good hospital practice dictates all instruments be inspected for visible debris after processing in the reliance synergy washer/disinfector.Any instrument with visible debris must be rewashed until clean and free of visible debris prior to terminal processing.Failure to reprocess until all visible debris have been removed may impede the terminal processing." the user facility confirmed they followed their department protocol for reprocessing instruments until clean and free of debris prior to terminal processing.No further issues have been reported.
|