The affected cable was investigation and it was found that heat was emitted from the power supply connector or jack of the connect 2 box.The wire diameter of the cable was also measured.This determined that it is sufficient for the 4a fuse of the cobas p 612.In the case of a short circuit, the fuse will switch off the circuit.As the cable was entirely melted, no further investigation on the returned material is possible.The following are the most probable causal factors of the issue: 1) a weakened or damaged cable, defective insulation or wire.The short circuit is below 4a.The source of damage is unknown but it cannot be completely excluded that it was possible to happen at the manufacturer, production, or during installation.2) contact of hanging cable with grounded parts or with the connector of the ethernet cable, so that a permanent current flows leading to the emission of heat.3) polluted or contaminated cable jack.The most probable causal factor of the pollution is the environmental conditions of the instrument.The investigation could not identify a product problem.The cause of the event could not be determined.
|