A medivators service technician arrived onsite to inspect the unit and found that a basin regulator cracked causing the reported leak.The unit was installed in 2015 making it approximately 7 years old and is not under medivators service agreement; the user facility is responsible for all maintenance activities.The dsd edge operator manual states (9), "on a monthly basis (or if a leak is detected), inspect the reprocessor for basin damage or pipe and tubing damage, which may result in leaks." the technician replaced the regulator, tested the unit, confirmed it to be operating according to specification, and returned it to service.No additional issues have been reported.
|