Philips investigated this complaint and came to the following conclusion: the detector chiller leaked fluid into the power strip below causing the cabinet to catch fire, which self extinguished when power was removed.This resulted in damage to the r-cabinet and components.Due to a leak in the detector cooling system, cooling liquid may leak outside the drip tray of the chiller.If this occurs the liquid may drip onto electrical components in the r-cabinet located in the technical room, which could lead to damage to the system and potentially cause thermal events such as a burning odor, smoke or fire.Philips initiated a field safety corrective action fco 72200384 which is targeted towards root cause cooling fluid leaking onto the connector.This field safety corrective action was filed to the fda on 2017mar22.
|