The issue was investigated in detail.During system installation at this site it was found that the front cover failed grounding resistance test.This grounding resistance test is also performed during the factory final testing and it was found within acceptable thresholds on this particular unit.During transportation and time lapse between operations the resistance between system parts may slightly increase in comparison to the measurements before (e.G.Oxygen film).According to the local service this cover yielded a measurement value of 0.55 ohm, however, after cleaning with a wire brush the cover yielded a value of 0.07 ohm, which is still an acceptable value.Checking and correcting of the grounding resistance is a required step during installation, maintenance and reactive service.Additional system covers were tested on the production line and it was determined that they all fulfill the maximum resistance thresholds.If after system delivery the grounding resistance measures are above the threshold, the system will not be handed over to the customer.The investigation showed that no risk is known from the field.No general problem, hazard or injury was communicated due to grounding resistance failure.However, the cover at this facility was replaced as a precaution.This report was submitted december 1, 2017.
|