S/w 3.0b.On (b)(6) 2022 the customer passed away.The pump passed the functional test, including the displacement test, rewind, basic occlusion test, occlusion test, prime/a33 test, excessive no delivery test and dat at 0.0873 inches.The stop (idle) current and run current measurement tests are within specification.The pump also passed self test, off no power alarm test and a21 error test.The pump had intermittent button response on the esc, act, up arrow and down arrow buttons due to flattened dome switched (no crease).No button error alarm noted during testing.There was no data listed on the event date in the pump's alarm history screen or in the formatted history file.Unable to confirm time/date of alarm in the pump's alarm history screen or in the formatted history file.The following were noted during visual inspection: minor scratched display window, scratched case, cracked reservoir tube and cracked reservoir tube lip.The test p-cap and reservoir does lock in place in the reservoir compartment.History download was successful using thds and carelink upload was successful.The pump did not have a battery installed when received.Please see below when reviewing the history download.There is no data available due to the pump was stored for an extended period without a battery.The pump passed the functional testing.However, the pump had intermittent buttons due to flattened dome switches on the keypad assembly was confirmed.(b)(4).
|